RU EN

IKV-1-2-1 type A vibration measuring channel

IKV-1-2-1 type A vibration measuring channel

Designed for measurement of the root mean square (RMS) value of vibration velocity in emergency protection systems (EPS);

Consists of DV-1 (type 00, 02) vibration transducer, AV 121 charge amplifier and a TIK-BIS.1X1 safety barrier installed in the connecting box (the box and the barrier are delivered at the request of the Customer);

DV-1 vibration transducers are supplied with anti-vibration cable;

Output signal type – 4-20 mA






Additional photos

Reviews

Related equipment

TIK-PLC 112
controller
TIK-BIS
safety barriers

specifications

Metrological parameters

  • Conversion coefficient, mA*s/mm / Range of indications of RMS vibration velocity, mm/s
    16 / 0-1
    5.333 / 0-3
    1.6 / 0-10
    0.8 / 0-20
    0.533 / 0-30
    0.32 / 0-50
    0.16 / 0-100
  • Operating frequency range, Hz
    2-1000
    10-1000

Interface

  • Output signal type
    "current loop" 4-20 mA
  • Supply voltage range, V
    10-24

Explosion protection

  • Kind
    intrinsically safe circuit
  • Marking
    0Ex ia IIC T6...T1 Ga X (DV-1 vibration transducer)
    not lower than 0Ex ia (AV 121 charge amplifier)
  • Connection
    through TIK-PLC 112 controller
    through TIK-BIS safety barrier

Design parameters

  • Version
    IKV-1-2-1 type A (DV-1 type 00 vibration transducer or
    DV-1 type 02 vibration transducer, AV 121 charge amplifier,
    optional - TIK-BIS.1X1.0X0X safety barrier, connecting box)
  • Overall dimensions, mm
    Ø39.25x39.5 (DV-1 vibration transducer)
    98.5x27.5x59 (AV 121 charge amplifier)
  • Weight, kg, not more than
    0.2 (DV-1 vibration transducer)
    0.1 (AV 121 charge amplifier)
  • Mounting type
    screw M4x21 (M4x28) 3 PCs.
  • Protection class
    IP65/IP68 (DV-1 type 00 vibration transducer)
    IP65 (DV-1 type 02 vibration transducer)
    IP20 (AV 121 charge amplifier)

Operating parameters

  • Operating temperature range, ºС
    -40...+150 (DV-1 vibration transducer type 00/02)
    -60...+150 (DV-1 vibration transducer type 00/02, cold version)
    -60...+70 (AV 121 charge amplifier)

Reliability parameters and manufacturer's guarantees

  • MTBF, hours, not less than
    40 000
  • Warranty service life, months
    24
  • Service life, years, not less than
    10
  • Installed device life, hours, not less than
    80 000
  • Time between verifications
    1 years
Service center