RU EN
Certificate ISO 9001

IKV-1-3-1 vibration measuring channel

IKV-1-3-1 vibration measuring channel

Designed to measure the vibration displacement span in diagnostic and emergency protection systems (EPS)*;

It consists of a DS-1 (DS-2, DS-3) eddy-current transducer and AS131 converter (in the connecting box), or AS1312 converter on the connecting cable.

Application on the compressor equipment is possible;

Output signal type – 4...20 mA;

*By default, the channel is set to 40X metal




Related equipment

TIK-PLC 112
controller
TIK-BIS
safety barriers

Additional photos

Reviews

specifications

Metrological parameters

  • Conversion coefficient, mA/μm / Range of indications of amplitude of vibration displacement, μm
    0-125, 0-250 (eddy-current transducer DS-1 (M8x1))
    0-100, 0-250 (eddy-current transducer DS-1 (M10x1))
    0-500, 0-1 000 (eddy-current transducer DS-2)
    0-2 000 (eddy-current transducer DS-3)
  • Operating frequency range, Hz
    2...500
  • Installation gap (default), mm
    1.0±0.2 (eddy-current transducer DS-1 (M8x1))
    1.5±0.2 (eddy-current transducer DS-1 (M10x1))
    3±0.2 (eddy-current transducer DS-2)
    5±0.2 (eddy-current transducer DS-3)

Interface

  • Output signal type
    "current loop" 4...20 mA
  • Supply voltage range, V
    10...24

Explosion protection

  • Kind
    intrinsically safe circuit
  • Marking
    0ExiaIICT6 (eddy-current transducer DS-1, DS-2, DS-3)
    0ExiaIICT5 (connecting box)
  • Connection
    through TIK-PLC 112 controller
    through TIK-BIS safety barrier

Design parameters

  • Version
    IKV-1-3-1 ver. A (eddy-current transducer
    DS-1 (DS-2, DS-3) ver.00 or 01 (with connector),
    AS131 converter, connecting box,
    TIK-BIS safety barrier)


    IKV-1-3-1 ver. B (eddy-current transducer
    DS-1 (DS-2, DS-3) ver.02 with connector and converter
    AS1312 on the cable), connecting box,
    TIK-BIS safety barrier)

  • Overall dimensions, mm
    D(6.8) L(50; 70; 90) (eddy-current transducer DS-1 (M8x1))
    D(8.5) L(50; 70; 90) (eddy-current transducer DS-1 (M10x1))
    D (14.5) L(50; 70; 90) (eddy-current transducer DS-2)
    D (22.5) L(90) (eddy-current transducer DS-3)
    98.5x27.5x59 (AS131 converter)
    277x217x84 (connecting box)
  • Weight, kg, not more than
    0.35 (eddy-current transducer DS-1)
    0.4 (eddy-current transducer DS-2)
    0.5 (eddy-current transducer DS-3)
    0.1 (AS131/AS1312 converter)
    2.5 (connecting box)
  • Mounting type
    threaded hole M8x1 (eddy-current transducer DS-1)
    threaded hole M10x1 (eddy-current transducer DS-1)
    threaded hole M16x1 (eddy-current transducer DS-2)
    threaded hole M24x1 (eddy-current transducer DS-3)
  • Protection class
    IP67 (eddy-current transducer DS-1, DS-2, DS-3)
    IP20 (AS131 converter)
    IP66 (connecting box)

Operating parameters

  • Operating temperature range, ºС
    -40...+135 (eddy-current transducer)
    -60...+135 (eddy-current transducer, climatic version HL)
    -40...+70 (AS converter)
    -60...+70 (AS converter, climatic version HL)

Reliability parameters and manufacturer's guarantees

  • Mean time between failures, hours, not less than
    10 000
  • Warranty service life, months
    18
  • Service life, years, not less than
    10
Service center